Testing 320 kV HVDC XLPE Cable

Cables & Accessories, HV/HP Testing

Leer artículo en español

There are two unique test requirements in testing a high-voltage direct-current (HVDC) cable system compared to high-voltage alternate-current (HVAC) cable system: a specified maximum temperature drop across the insulating layer of a cable (∆θ_max) and a superimposed impulse withstand test. Here, the focus is on this topic, based on practical testing experience. The temperature difference 〖∆θ〗_max (excluding the semiconducting screens) is provided by cable manufacturer depending on insulating material (e.g. XLPE: cross-linked polyethylene) as well as cable design. This temperature difference needs to be maintained in a specified limit during a stead state of a load cycle. In practice, it is not possible to measure ∆θ_max directly. By applying heat transfer theory, a simple formula is introduced to calculate 〖∆θ〗_max. A superimposed impulse withstand test is essential for a HVDC cable system to be qualified for two HVDC converter technologies, i.e. Line Commutated Converter (LCC) and Voltage Source Converter (VSC).

This edited past contribution to INMR by experts at KEMA Laboratories in the Netherlands, presented a laboratory test set-up for switching/lightning impulse (SI/LI) voltage superimposed on a HVDC voltage. A universal divider is introduced to measure combined stresses for HVDC cable system.

Advertisement

Thermal Physical Model

A temperature difference arises across the cable and temperature distribution inside can either be measured by thermocouples or calculated by a numerical model. Fig. 1 shows an equivalent thermal circuit for the cable, where:

Q, heat transfer rate (heat flow), W;
θc, θcs, θi, θis, θis, θamb, temperature of conductor, conductor screen, insulation, insulation screen, sheath and ambient, °C;
Δθcs, Δθi, Δθis, temperature drop across conductor screen, insulation and insulation screen respectively, K;
Δθc-is, temperature difference from conductor to insulation screen, K;
Tcs, Ti, Tis, thermal resistance of conductor screen, insulation, insulation screen respectively, K·m/W;
Ts, thermal resistance in total from metal sheath to over sheath, K·m/W;
Ttm, thermal resistance of external thermal insulation material, K·m/W;

Fig. 1: Diagram of equivalent thermal circuit for cable.

Temperature difference across conductor screen, insulation and insulation screen is calculated as follows:


θis, and θc are measured directly by thermocouples. Overall temperature difference from conductor to insulation screen is therefore:

Based on Eq (2) and (4),

Eq (5) is the simple formula for calculation of ∆θmax. Since the surroundings also play a role, the main temperature drop in a cable is between the cable surface (sheath) and environment (θs-θamb). In order to control ∆θi within the limit of ∆θmax, external thermal insulation material (e.g. plastic bubble) is applied to minimize influence of the environment. This thermal insulation material helps adjust Ttm based on different cable design and surrounding condition.

Advertisement

Load Cycle & Temperature Measurement

In order to monitor the thermal environment of HVDC cable system, thermocouples were placed at a total of more than 20 different locations on a reference cable and a test cable. The reference cable must be installed in close proximity with the test cable to ensure equal thermal environment. Conductor temperature of the reference cable (based on rated maximum θc, e.g. 70°C) was monitored to guide the same current applied to the test cable simultaneously. By applying Eq (5), specified Δθmax was calculated and monitored during the load cycle. Fig. 2 shows a typical 24 hours load cycle.

Fig. 2: Diagram of typical 24 h load cycle.
Fig. 2: Typical 24 hour load cycle.

Advertisement

Figs. 3 and 4 schematically demonstrate the cable cross-section (e.g. 2500 mm2) and the locations of the measured temperature respectively.

Fig. 3: A cross-section overview of cable construction.
Fig. 4: Locations of measured temperature.

Experimental Set-up

An experimental setup included a DC generator, an impulse generator and a test object, which was a 320kV DC cable system including HVDC XLPE cable (copper conductor and XLPE insulation, nominal capacitance of 0,26µF/km), two outdoor oil terminations and two premoulded joints with shield interruption. A schematic test circuit and a photo of a real test setup are shown in Figure 5 and Figure 6 respectively. Each test system was equipped its own divider in order to measure DC voltage (Divider 1 in Fig. 5) and SI/LI (Divider 3 in Fig. 5) respectively. A combined divider (Divider 2 in Fig. 5) was applied to measure the superimposed withstand voltage subjected directly to the test object.

A pair of spheres (diameter of 0,5 m, SG2 in Fig. 5) was installed in vertical position, the lower sphere directly fixed to the outdoor terminations. The DC generator was also connected to the lower sphere with the protection water resistor (10 MΩ, R1 in Fig. 5) and the blocking impedance (35 mH, L1 in Fig. 5) in between. The upper sphere was separated from the lower sphere and the cable by an air gap and connected to the impulse generator. The surge arrestor (A1 in Fig. 5 ) was installed for extra protection of the DC generator.

Fig. 5: Schematic view of the test circuit for superimposed impulse test of DC cable system.
Fig. 6: Test set-up of 320 kV DC cable system.

Test Procedure

Accurate measurement of voltage waveforms and self-ignition of sphere gap are the two essential aspects for a superimposed impulse test. By means of a sphere gap, this gap must ignite at a certain level and transfer the SI/LI to the cable system. The gap distance has to be considered and adjusted. Under the same polarity of two voltages (e.g. + UDC and + USI, a unipolar stress), the breakdown voltage of the sphere gap (Ubd unipolar = UDC – USI ≥ UDC , thus USI ≥ 2 UDC), in contrary to a bipolar stress (e.g. + UDC and – USI), the voltage (Ubd bipolar = UDC – (– USI) ≥ UDC , thus absolute USI ≥ 0). Therefore under the bipolar stress, there is not critical for breakdown the air gap; however under the unipolar stress, it is a complex procedure due to the Ubd unipolar. Furthermore, this calibration steps are necessary to avoid overshot of the test object [4]. The distance of sphere gap needs to be adjusted corresponding with the calibration of impulse voltages from low scales (50%, 65% and 80% of the test voltage) up to full scale (100% of the test voltage).

Analysis of Measured Results

The three measured voltages were obtained with three dividers D1, D2, D3 (see Fig.5) during the testing. The DC voltage measured by the Divider 1 via a digital voltage meter and the full scale of DC voltage should be 320kV. The SI/LI voltages were overserved by the Divider 3 and the peak voltages should be 710kV and 740kV respectively (see Fig.7). DC voltage superimposes with same polarity of SI is shown in Fig. 8. It is further found that DC voltage superimposes with opposite polarity SI and LI in Figs, 9 and 10 respectively.

Fig. 7: Representations of the switching impulses waveforms measured by Divider 3.
Fig. 8: The unipolar stress (UDC and USI ) measured by Divider 2.

Fig. 9: The bipolar stress (UDC and USI) measured by Divider 2.
Fig. 10: The bipolar stress (UDC and ULI) measured by Divider 2.

In Fig. 7, the Divider 3 measured a spike in front of the SI wave shape, which is the time delay of the protection sphere gap, it was until over the breakdown voltage, then sphere gap was conducting and the cable system was connected at that moment to the impulse generator.

It is observed in Fig. 8, a systematic DC offset error occurs during the tests. The Divider 2 was calibrated by DC voltage and Impulse voltages respectively. For combined voltages, a correction factor is needed (i.e. a factor of 0,78). This offset leads to a difference of peak voltages of impulses measured by Divider 3 and Divider 2.

It is noticed that, once the arc between the spheres was ignited, the voltage on the cable system followed the voltage at the terminal of the impulse generator. Thus the voltage on the cable system in extreme short time (hundreds or thousands of µs) discharged via impulse generator to extinguish voltage of the arc (visible in graphs), then it would take short recover time (few hundreds of ms) to recharge to the DC voltage (invisible in graphs due to limitation of data collection). In the meantime, the protection resistors sustained the full difference of impulse voltage and DC test voltage.

Advertisement

Conclusions

The calculation of Δθmax is obtained based on heat transfer method. In order to maintain a constant surface temperature of the cable, needed to guarantee a specified Δθmax , the practice methods are to control load current through conductor, maintain constant ambient temperature or apply the external thermal insulation material.

A proper test setup using a sphere gap has been developed for the application of SI/LI superimposed on a DC voltage. The correct gap adjustment is essential for unipolar stress condition, otherwise under certain circumstances, the high-frequency oscillations might occur.

Further experimental work will focus on a method of controlling cable sheath temperature, and developing a new three-channel software with extended data capture time (up to recover time of DC voltage). Furthermore, a protection capacitor is another alternative of a sphere gap to realize the superimposed withstand test.

References
[1] Cigre 496: Recommendations for Testing DC Extruded Cable Systems for Power Transmission at a Rated Voltage up to 500kV, April 2012.
[2] IEC 62895 Edition 1.0: 2017-05: High voltage direct current(HVDC) power transmission – Cables with extruded insulation and their accessories for rated voltages up to 320 kV for land applications – Test methods and requirements.
[3] E. Pultrum, W. Sloot, J. Fernandez, R. P. P. Smeets, “High-voltage cable testing: type test experiences and new insights into pre-qualification”, CEPSI, 2016.
[4] IEC 60060-1 Edition3.0: 2010-09: High-voltage test techniques – Part 1: General definitions and test requirements.

FEATURED SUPPLIER:

More about EC Insulator

INMR LABORATORY GUIDE


More about Mechanical Tests