MOV Protection of Series Capacitor Banks

Advertisement
PPC Insulators capacitor bank MOV Protection of Series Capacitor Banks banner530x150 modified

Series capacitor banks serve the purpose of increasing power flow on an existing power system by reducing line impedance and basically consist of capacitors as well as their protective system. Their application dates back to 1928 when the first such bank – rated at 1.2 MVar – was installed at the Ballston Spa Substation on the 33 kV grid at New York Power & Light. Since then, series capacitor banks have been installed on systems all over the world. MOVs provide the overvoltage protection and therefore are a significant component of these banks. Jonathan Woodworth, an arrester specialist in the United States examines this important role.


Overview

When capacitors are inserted into a transmission system, the series capacitance effectively compensates for the inherent inductance of the line so as to lower total impedance. In effect, this allows the circuit to transfer more energy with a lesser heating effect. Such series banks are generally located at either end of the transmission line section at one of the existing substations. Sometimes, however, they are located near the middle of the line in order to reduce the worst-case potential fault current. With lower potential fault current, the metal oxide varistor (MOV) bank can be designed smaller. Today, with the increasing difficulty in obtaining right-of-ways for new power lines coupled with the rising cost of building lines, use of a series capacitor bank is increasingly seen as a favorable option. Moreover, for long transmission lines, where source and load are separated by great distance, use of fixed series compensation (or FSC) has now become a virtual necessity.

Series capacitor bank in Brazil showing all three phases on 500 kV platforms. capacitor bank MOV Protection of Series Capacitor Banks Series capacitor bank in Brazil showing all three phases on 500 kV platforms
Fig. 1: Series capacitor bank in Brazil showing all three phases on 500 kV platforms.
CLICK TO ENLARGE
Segment of series capacitor bank installation showing MOV units (front), triggered gap (in box in back right) and capacitors (to left of triggered gap). capacitor bank MOV Protection of Series Capacitor Banks Segment of series capacitor bank installation showing MOV units
Fig. 2: Segment of series capacitor bank installation showing MOV units (front), triggered gap (in box in back right) and capacitors (to left of triggered gap).
CLICK TO ENLARGE

As seen in Fig. 1, a series bank is typically mounted on a platform and while in service the entire structure above the insulators is energized at system voltage. The series capacitor platform is connected to the control computer via fiber optic links that effectively isolate the protection controls from the high voltage. The typical protective bypass system consists of a metal oxide varistor, bypass gap, damping reactor and bypass circuit breaker. The varistor serves to provide overvoltage protection during power system faults. The bypass gap is then controlled to spark over in the event of excess varistor energy while the bypass breaker closes automatically in the case of prolonged gap conduction or other platform contingencies. The breaker also allows the operator to insert or bypass the series capacitor. The damping reactor limits the capacitor discharge resulting from gap sparkover or bypass breaker closure.

The varistor and the triggered gap operate independently on each phase while the bypass breaker operates on a threephase basis. The bypass system is capable of operating with single-pole or three-pole tripping and re-closing schemes employed on the transmission lines.

Advertisement
capacitor bank MOV Protection of Series Capacitor Banks CSL Advertisement e1477326535980

Protective Role of MOVs

The varistor role in the protection of capacitors in these applications is simple and at the same time unique. Simple, because the arresters are installed for one purpose only – to limit the voltage across the capacitors during a fault on the system. And unique because, while limiting the voltage during a fault, they also conduct a large portion of the fault current. In fact, there are very few other arrester applications where conduction of power frequency fault current is the responsibility of the arrester. Conducting fault current for 50-100 ms is much different from normal switching and lightning overvoltage events that are over in a few microseconds to a millisecond. Since the MOVs are connected in parallel with the capacitors at all times, they do not need any special signal to enter the protection scheme. They are always ready and, if there is a fault on the system, the MOV is immediately available to protect.

Schematic of series capacitor bank. capacitor bank MOV Protection of Series Capacitor Banks schematic of series capacitor bank
Fig. 3: Schematic of series capacitor bank.
CLICK TO ENLARGE

The highly unusual aspect of this MOV application is that the MOVs are themselves protected by electronic controls as well as the triggered bypass gap. The protection controller monitors the current through the MOVs at all times. If at any point the recently accumulated energy exceeds the rating of the MOV bank, the bypass gap is triggered. This gap is capable of operating and redirecting the fault current away from the MOVs within as little as 1 to 2 ms. In Fig. 4, a three-phase fault is modeled and shows the current through the MOV and capacitors during such an event. Note that the capacitor bank conducts the current for the first half cycle while the MOV conducts the current for the second half. This is due to the non-linearity of the MOV.

capacitor bank MOV Protection of Series Capacitor Banks inmr 8
Fig. 4: 3 phases of MOV and capacitor current during fault.
CLICK TO ENLARGE

During a fault event, the MOV conduction results in absorption of energy as shown in Fig. 5. This energy absorption is constantly being monitored and forms the basis for triggering the bypass gap.

Graph of MOV energy absorption during 3 phase fault. capacitor bank MOV Protection of Series Capacitor Banks Screen Shot 2019 01 21 at 13
Fig. 5: MOV energy absorption during 3 phase fault.
CLICK TO ENLARGE

There are basically two types of faults of concern for series capacitor installations. If the fault occurs within the section of transmission line where the bank is located, it is referred to as an internal fault (see Figure 3) while should a fault occur on another section of line, it is considered an external fault. The difference between the two is only the magnitude of the fault. A nearby internal fault will result in significant fault current and significant duty placed on the varistors. A distant fault on an external section can result in a current only a few percent higher than the maximum rated for the capacitor bank. These two faults are therefore handled differently by the control system and the MOVs.

If the control system senses a high current internal fault, it sends a signal to the triggered gap to bypass immediately. This pulls the MOVs out of the circuit before any significant accumulation of energy can take place. When an external fault occurs, the protection controls are all that the MOVs have between operation and overload. If the control system fails, it is likely that the MOVs will fail as well. To achieve a high energy absorption capability, MOV columns are mounted in parallel. Fig. 6 shows a sizable bank of arresters used to protect a series capacitor installation.

MOV columns protecting series capacitor bank. capacitor bank MOV Protection of Series Capacitor Banks Screen Shot 2019 01 21 at 13
Fig. 6: MOV columns protecting series capacitor bank.
CLICK TO ENLARGE

Specifying MOV Banks for Series Compensation Systems

The suppliers of series capacitor banks are generally also the specifiers of all components used in the installation. The characteristics of the MOV columns are arrived at using an iterative process during a comprehensive system study developed specifically for these applications. This type of study is unique for each installation and is based on the system fault current and operating schemes, as indicated by the end user utility. The size of the MOV bank is a function of many variables and sophisticated models have been developed to speed up and improve the quality of the specification. Once the series capacitor bank supplier has run numerous models and determined the optimum size of the varistor bank, they typically turn to the MOV supplier for the final design and configuration specifications.

Advertisement
BPG International Advertisement capacitor bank MOV Protection of Series Capacitor Banks BPG Banner

Dimensioning MOV Banks

The banks of MOV columns have several critical criteria that need to be met for them to operate properly over the life of the series bank. These characteristics include maximum energy absorption capability, maximum peak current capability, maximum clamping voltage at the highest fault current, minimum re-insertion time, matched ageing characteristics and matched voltage/current (VI) characteristics. The required Maximum Energy Absorption capability and the desired clamping voltage are often the primary factors determining the number of columns used in an MOV bank. Based on testing and historical performance, the MOV supplier knows the maximum energy absorption capability of each disk and column used in this type of application. The energy requirement in this case is very different from standard lightning and switching energy capabilities.

Besides absorbing energy over relatively long periods of time (100 ms vs. 2 ms), the columns are in parallel and share the current according to their design. The maximum energy of the group of parallel columns is a simple sum of the energy absorption of each disk times the energy de-rating factor used in the design.

Advertisement
capacitor bank MOV Protection of Series Capacitor Banks INTEGRATED Engineering Software Mar 11

Matched VI Characteristics or Maximum Current Sharing Deviation is guaranteed by the MOV supplier. It is verified in the routine tests performed on all MOV banks and is also the most demanding task when manufacturing this type of MOV product since it requires painstaking data collection and time-consuming tests to verify and adjust to match.

capacitor bank MOV Protection of Series Capacitor Banks Screen Shot 2019 01 21 at 13
CLICK TO ENLARGE
Typical VI curve of MOV column. capacitor bank MOV Protection of Series Capacitor Banks Screen Shot 2019 01 21 at 13
Fig. 7: Typical VI curve of MOV column.
CLICK TO ENLARGE

First, the VI characteristic of each disk is measured at several points on its VI curve. A typical such VI characteristic of a MOV column is provided in Fig. 7 and shows the range over which it is important to match it. Above that range, matching is not useful since it is not likely to be a current level the column will ever experience. The area above the critical matching range is in the lightning protection range. The area below the matching range is also not of much importance, since the current and losses in that region are insignificant and would not lead to any heating imbalance in the bank. If three points along the VI curve can be matched when assembling a MOV column for this application, the bank will be perfectly matched. If three points between two columns are matched, then it guarantees that the routine matching test will succeed. If two points are matched, it is possible to succeed in the verification test, but no longer guaranteed. If only one point is matched, then success in the test is not likely. These points are accurately matched using sorting schemes unique to each manufacturer. Once the matched columns are partially assembled, each column is impulsed at a current in the range it will operate and compared to all other columns to which it will be mounted in parallel. If the segment or phase calls for 300 matched columns, the comparative test is performed on 300 columns.

This routine test is required by IEC and IEEE standards and the results are used to guarantee the specified matching characteristics. Because MOV disks and columns are very nonlinear, measuring the residual voltage during a comparative test does not produce sufficiently accurate current sharing data – only the current through the column can be used for the comparison. Also, since it is unrealistic to test 300 columns in parallel and measure the current through each simultaneously, usually only 10 to 20 are tested at one time and the groups compared to reference samples. This testing technique is basically common to all manufacturers and yields accurate matching.

Maximum Peak Current Capability is also well known by MOV suppliers based on historical applications and tests. This characteristic becomes important if the MJ rating of the bank is low but the fault current requirement is high. Once the MOV bank is designed, the maximum column current is simply the total maximum fault current divided by the number of columns. If the maximum capability of the MOV column is exceeded, the number of parallel columns needs to be increased.

Maximum Clamping Voltage, also known as the protective voltage at maximum fault current, is used to determine the maximum protective level of the bank. This value is important because it is the fundamental role of the MOV bank. The maximum clamping voltage at maximum fault current must be below the withstand level of the capacitor.

Capacitor withstand levels are essentially a function of the insulation and configuration of the capacitor bank. If the capacitor bank is to survive the expected life of the installation, this value must be well known and absolutely guaranteed. The maximum protective level of a series capacitor bank is the ratio between the peak voltage across the MOVs during a maximum fault event divided by the peak value of the voltage across the capacitors at rated continuous current. Typical such protective levels are 2.0 to 2.5.

Minimum Re-insertion Time is an increasingly important characteristic of this application. In fact, it is so important that some utilities have chosen to install redundant banks specifically never to be caught without series compensation on the system. Apart from the transmission line running at a lower maximum power flow, utility revenues are adversely affected if a bank is out of service and sometimes system stability is also lost.

MOV bank capacitor bank MOV Protection of Series Capacitor Banks Screen Shot 2019 01 21 at 13
Fig. 8: Typical cool down curve for MOV bank.
CLICK TO ENLARGE

Re-insertion time is a function of the thermal cool down speed of the polymeric-housed MOV column. In Fig. 8 it can be seen that, with a starting temperature of 160° C in an ambient of 40°C, a polymeric-housed MOV column can cool down to within 20°C of ambient in about 4 hours. Since most porcelain MOVs have four columns of disks inside one housing, they generally have a slower cool-down time than polymeric designs.

Matched Ageing Characteristic is another important characteristic of MOV banks. All MOV material changes over time when energized. These changes are in the low voltage region of the VI curve and therefore do not affect the clamping voltage of the column. However they can affect losses or matching characteristics at lower voltages.

If one column ages differently from another, it is feasible that the current matching and energy sharing can fall out-of-balance. This imbalance could then lead to premature failure of the bank due to overload of one column during a fault. Equal ageing is achieved by the manufacturer using disks with the same impulse and processing history covering the entire segment or parallel group.

Special Testing of MOVs for Series Compensation Systems

IEC standard 60143.2-1994 and IEEE 824-1994 are the two mature and comprehensive standards covering the protective equipment of series capacitor banks. While these standards are not unified, they are similar with both calling out type or design tests as well as acceptance and routine tests. For design tests, all the fundamental bank characteristics are covered. Type tests are then carried out on single columns that have been pro-rated from a voltage and current perspective. The required tests consist of residual voltage verification (clamping voltage characteristic), accelerated ageing, current sharing, energy absorption and pressure relief (if requested by the customer). It is important that the energy absorption test be demonstrated for both short-time (sub-cycle) as well as for long-term fault events (5-10 cycles). Longer term fault events stress MOV material differently than any other type of stress encountered in other applications. Given any inherent defects, such long-term stress can trigger failures in the MOV material that short-term events do not.

Routine Tests

Routine tests are not specifically called out in standards and are left to the discretion of the manufacturer. Still, they need to be robust enough to weed out all defects that could otherwise cause a failure in this unique application. In the case of an arrester used for lightning and switching surges, multiple square wave surges within a short period of time and with sufficient energy level are generally used to verify arrester quality. But for MOV disks used in series capacitor applications, the routine tests need to demonstrate both single pulse 8 ms surges and multi-cycle 8 ms pulses since both will be required to protect under these conditions. These extra energy tests are in addition to the normal residual and Vref tests that must be carried out.

Advertisement
Yizumi Ad capacitor bank MOV Protection of Series Capacitor Banks INMR YIZUMI July edition

Installation Considerations

Installation configurations are typically a function of platform dimensions, MOV dimensions and clearances as well as metering requirements. It is desirable to use the minimum possible space for the MOV columns so as to allow for a reduction in size of the platform. Since MOV columns are always at the same potential as the columns around them, clearances can be much smaller than in standard arrester applications. A second consideration during installation is to appear as one single MOV, meaning the connecting bus work should be of minimum inductance and resistance. (Note the robust bus work on the top and bottom of the arresters in Fig. 6.) Yet another important consideration in mounting MOV columns is metering leakage current in order to monitor the MOV’s state of health. Of course, since monitoring each column on large banks is not economic, groups of columns are mounted on separate bases. This way, the leakage current of one group can be compared to that of an equal group. If the values are different, then inspection is recommended.

Advertisement
Desma Advertisement capacitor bank MOV Protection of Series Capacitor Banks Desma banner Apr 26

Failure Modes & Considerations

Dealing effectively with the failure of a single column has long been a concern for users of MOVs in series capacitor protection. The main issue here is that, once the bank is energized, it begins ageing. The effect of such ageing is really only an issue if there is a partial failure of the segment. Since the segment is matched from the start and all columns within the MOV bank have aged at the same rate, it’s nearly impossible to substitute one column within a group and do this in such a way that current would continue to be shared equally. From the early days of MOV protection of series banks, the solution to this has been to install spares in each bank of columns that are put into service at the same time as the original columns. These so-called ‘hot spares’ see the same fault duty and same voltage profile over the life of the bank. With this solution, should there be a failure in the bank, it becomes a matter of simply extracting the failed column and re-energizing the bank. Collateral damage is another concern in the failure mode of large banks of MOV columns (see Fig. 9). For single column, polymer-housed units, any such collateral damage is not expected to be so significant and the risk of exceeding the hot spare quantity is not high.

capacitor bank MOV Protection of Series Capacitor Banks Single column failure and collateral damage on porcelain housed unit
Fig. 9: Single column failure and collateral damage on porcelain-housed unit.
CLICK TO ENLARGE
Fig. 10: Series capacitor bank with MOV protection in cold climate capacitor bank MOV Protection of Series Capacitor Banks Series capacitor bank with MOV protection in cold climate
Fig. 10: Series capacitor bank with MOV protection in cold climate.
CLICK TO ENLARGE

Conclusions

The utility industry is seeing growing use of series capacitor banks due to the demand for more efficient power transmission and also lower costs. This in turn is being driven by the popular move toward ‘green solutions’ and is a perfect example where, while a product itself may not qualify as green, its green effect can still be significant. Without MOV columns, series capacitor installations would be considerably more expensive and perhaps not even feasible. A clear trend in this application is conversion of housings to polymers in place of porcelain – a trend that was seen in other MOV arrester applications as well. This move has been driven by ease of installation since rigging equipment is not necessary, by less risk of collateral damage in event of failure and by the potential for reducing size of banks. In fact, it can be said that porcelain-housed MOV protection for series capacitor banks is now virtually at end-of-life. Wherever there is considerable separation between generation and demand for power, there will be a need for lengthy transmission lines. These lines are then inherently inductive because of the long conductors and this inductive component will need compensation, no matter where a line is located and whether cold climate or hot.

Advertisement
capacitor bank MOV Protection of Series Capacitor Banks OFIL banner 300X125 July1