Widespread Blackout Triggered Study of Contaminated Snow on Insulator Strings

On 22 Dec. 2005, a severe snowstorm in northern Japan led to one of the country’s worst long-term outages in decades and impacted the Niigata Kaetsu region supplied by Tohoku Electric Power Co. About 650,000 households were affected over a maximum duration of as much as 31 hours. For a country such as Japan, with among the highest reliability levels in the world, this was truly an extraordinary event.

The massive blackout was induced by wet snow mixed with sea salt that had packed the sheds of porcelain long rod insulators on both 66 kV and 154 kV lines. Conductor galloping along 275 kV transmission lines also contributed to the scale of the problem. In this case, the wet snow accreted on insulators and filled the gaps between sheds due to the effect of strong winds. Because the snow contained large amounts of sea salt, the insulation strength of the strings deteriorated rapidly and led to numerous flashovers – but in a way quite different from the better-known phenomena of ice accretion or snow cover on insulator strings.

While much research has been performed on ice accretion/snow accumulation on insulators, knowledge related to the effect of wet snow containing contamination such as sea salt is still comparatively rare. More research is therefore necessary to clarify the mechanisms of failure and establish the most effective countermeasures.

This INMR article from 2010 based on a contribution by Manabu Sakata of Tohoku Electric Power and Hiroya Homma of Japan’s Central Research Institute of Electrical Power Industry (CRIEPI), provided a valuable overview of the event. It also discussed the properties of wet snow accretion on insulator strings based on the results of artificial wet snow tests. All this was part of a project dealing as well with wet snow accretion on conductors as well as conductor galloping.


Introduction

In late December of 2005, a powerful low-pressure system from the Pacific moved south to north along the east coast of Japan’s main island while another similar system in the Sea of Japan crossed the island. Ambient temperatures in the Niigata Kaetsu area, on the island’s northwest, stabilized in the range of 0 to +2°C with a combination of heavy precipitation and wind. Total precipitation and maximum 10 min. average wind velocity were 26 mm and 14 m/sec respectively (with an overall maximum wind speed of over 25 m/ sec). Cascading electrical failures on 66 kV and 154 kV lines started just before 09:00 and resulted in numerous tripped lines. At the same time, some 275 kV transmission lines also began to trip out due to conductor galloping. Eventually, 30 transmission lines and 49 circuits were affected.

Advertisement
GIG Advertisement insulator string Widespread Blackout Triggered  Study of Contaminated Snow on Insulator Strings GIG Jun 28

Maintenance workers discovered that many of the porcelain long rod insulators used on the affected 66 kV and 154 kV lines were packed with wet snow. Figs.1a and 1b show examples of this on insulator strings as well as on a gap-type arrester. The shapes of packed snow on insulators in some cases were cylindrical while in other cases were eccentric pennant into the wind direction. These shapes of snow on insulator strings are quite different from those that result from simple ice accretion or snow cover. For example, the volume density of the packed snow ranged from 0.54 to 0.94g/cm3 while its maximum conductivity was approximately 0.2 mS/cm.

Fig. 1a: Examples of packed snow on horizontally-mounted long rod insulator strings. insulator string Widespread Blackout Triggered  Study of Contaminated Snow on Insulator Strings Screen Shot 2018 10 14 at 13
Fig. 1a: Examples of packed snow on horizontally-mounted long rod insulator strings.
CLICK TO ENLARGE
Fig. 1b: Example of packed snow on vertically mounted long rod insulator strings and gap type arresters. insulator string Widespread Blackout Triggered  Study of Contaminated Snow on Insulator Strings Screen Shot 2018 10 14 at 13
Fig. 1b: Example of packed snow on vertically mounted long rod insulator strings and gap type arresters.
CLICK TO ENLARGE

The worst of the weather ended before nightfall and restoration work began at midnight. More than 2500 workers climbed the towers and removed the packed snow from insulator surfaces by hand. This proved very difficult since the wet snow had by then nearly transformed into ice and it took many hours for the affected electrical system to again be fully operational.

During restoration, numerous traces of power arcs on insulator surfaces and hardware were observed on both horizontally and vertically mounted insulators, including V-strings. These were found over a broad area, even as much as 30 to 40 km inland. In fact, measured conductivities of the packed snow were actually highest in this area as sea salt was apparently carried inland by the powerful winds.

Tohoku Electric Power Co. completed change-out of the long rod insulators of one circuit in the affected area to cap & pin strings and have since adopted the same countermeasure in other regions where similar events seem possible in the future.

Advertisement
insulator string Widespread Blackout Triggered  Study of Contaminated Snow on Insulator Strings Zibo ad 14

Impact on Insulators of Wet Snow with Sea Salt

This blackout event was induced by heavy, high conductivity snow combined with strong winds – a climatic condition quite different from that which usually deposits ice accretion or snow cover. Similarly, the affected lines ran along coastal and inland plains instead of traversing snow-covered mountains. Moreover, the electrical failures occurred during the snow accretion process itself whereas failures due to simple ice accretion and snow cover usually take place after sunrise as ambient temperatures begin to increase. It can therefore be concluded that the phenomena behind this event are quite distinct from the better-known ice accretion or covered snow that occurs on insulator strings.

Table 1 summarizes the typical features of wet snow packed with sea salt compared with simple ice accretion and covered snow.

insulator string Widespread Blackout Triggered  Study of Contaminated Snow on Insulator Strings Screen Shot 2018 10 14 at 13
CLICK TO ENLARGE

Since dealing with this type of problem requires an understanding of the basic properties of the process, an artificial wet snow accretion test was carried out in January 2008 to clarify the mechanism of failure caused by wet snow packed with sea salt. The purpose of the test, which took place at a wind generator test station in Niigata, was to evaluate the basic properties of wet snow accretion on insulators having different shed profiles. As experience with packed wet snow is still limited, the test was performed qualitatively.

Figures 2a and 2b show a schematic of the wind generator and test set-up.

Fig. 2a: Schematic of wind generator. insulator string Widespread Blackout Triggered  Study of Contaminated Snow on Insulator Strings Screen Shot 2018 10 14 at 13
Fig. 2a: Schematic of wind generator.
CLICK TO ENLARGE
Fig. 2b: Test set up. insulator string Widespread Blackout Triggered  Study of Contaminated Snow on Insulator Strings Screen Shot 2018 10 14 at 13
Fig. 2b: Test set up.
CLICK TO ENLARGE

Both dry and wet types of snow were used for the test, with the difference between the two consisting only of its liquid water content. LWC was adjusted by putting natural snow into a test room where ambient temperature was kept around 2°C. While the LWC of natural snow is about 0%, the LWC after adjustment was approximately 5 to 8%.

Table 2 shows the types of insulators used in the test. The 66 kV porcelain long rod, cap & pin and polymeric insulators were all tested in both horizontal and vertical configurations and their snow accretion properties studied and compared.

insulator string Widespread Blackout Triggered  Study of Contaminated Snow on Insulator Strings Screen Shot 2018 10 14 at 13
CLICK TO ENLARGE

Advertisement
insulator string Widespread Blackout Triggered  Study of Contaminated Snow on Insulator Strings CSL compressed

Test Results

Figure 3 shows a horizontally mounted long rod porcelain insulator after the test. Although a small number of snow particles were attached to its surface, these never grew into a large-scale accretion. This finding agrees with service experience that indicates outages caused by snow packed with sea salt are induced only by wet snow.

insulator string Widespread Blackout Triggered  Study of Contaminated Snow on Insulator Strings Screen Shot 2018 10 14 at 13
Fig. 3: Snow accretion for horizontally-mounted long rod insulator with dry snow (after the test).
CLICK TO ENLARGE
Fig. 4a: Snow accretion on horizontally mounted long rod insulator (after about 20 min). insulator string Widespread Blackout Triggered  Study of Contaminated Snow on Insulator Strings Screen Shot 2018 10 14 at 13
Fig. 4a: Snow accretion on horizontally mounted long rod insulator (after about 20 min).
CLICK TO ENLARGE

The process of snow accretion on conductors is already quite well known and is the result of two different combined mechanisms: one sees the snow accreted onto the conductor surface sliding slowly along the strands from its weight; the other sees the conductor itself rotate due to the weight of accreted snow. In the case of insulators, the process is basically the same although, since insulator strings are fixed to towers, the latter mechanism clearly does not apply.

insulator string Widespread Blackout Triggered  Study of Contaminated Snow on Insulator Strings Screen Shot 2018 10 14 at 13
Fig. 4b: Windward side (after the test). Fig. 4c: Leeward side (after the test). Fig. 4d: Packed snow after part is removed.
CLICK TO ENLARGE

In the case of the wet snowstorm in the Niigata area, the cylinder-like shape of packed snow was observed on both horizontally and vertically mounted long rod insulators. The shape of packed snow in this test, however, was developed on only the windward side of the insulator and therefore did not exactly reproduce the shape of packed snow observed in the field. On the other hand, the eccentric pennant shape of packed snow into the wind direction was also found on a polymeric gap type arrester during the Niigata storm. The differences in formation conditions and processes between the cylindrical shape and the eccentric pennant into the wind is not yet clear and will be left for future research.

insulator string Widespread Blackout Triggered  Study of Contaminated Snow on Insulator Strings Screen Shot 2018 10 14 at 13
Fig. 5: Process of forming cylindrical snow on horizontally mounted long rod insulator
(seen from the axis of insulator).
CLICK TO ENLARGE
insulator string Widespread Blackout Triggered  Study of Contaminated Snow on Insulator Strings Screen Shot 2018 10 14 at 14
Fig. 6a: Snow accretion on vertically mounted long rod insulator (after test). Fig. 6b & Fig. 6c: Examples of snow removed from insulator after test.
CLICK TO ENLARGE

Three important points were confirmed during this test.

1. The time for vertically mounted insulators to be bridged between the sheds was shorter than for horizontally mounted ones. In the vertical arrangement, the upper parts of sheds are quickly covered with snow and the sheds are easily bridged. This suggests that I-strings may be more prone to failure than either tension or dead-end strings. At the same time, many traces of power arcs were also found on horizontal insulator strings during the wet snowstorm. In this respect, field experience does not agree with test results and electrical failures may be related not only to wet snow accretion but also to various flashover mechanisms that still need to be clarified.

2. Movement of water to the bottom of packed snow was seen in this case (see Fig. 7 and 8) and could be related to the subsequent flashover mechanism.

insulator string Widespread Blackout Triggered  Study of Contaminated Snow on Insulator Strings Screen Shot 2018 10 14 at 13
Fig. 7: Movement of water inside snow.
CLICK TO ENLARGE
insulator string Widespread Blackout Triggered  Study of Contaminated Snow on Insulator Strings Screen Shot 2018 10 14 at 13
Fig. 8: Packed snow can rotate slowly but not be taken away easily.
CLICK TO ENLARGE

3. Once snow does bridge sheds, the packed snow cannot easily be removed from the insulator surface whereas before bridging the snow tends to be blown away by wind. Nevertheless, snow accretion progresses quite slowly along the insulator’s axial direction and this effect can be explained by the fact that the adhesive tensile strength of snowflakes is greater than their adhesive shear strength. Long rod insulators are not only more easily bridged by snow but the accreted snow is at the same time not easily removed by wind-induced vibrations in the field.

A test with wet snow (LWC 5% and volume density 0.3 g/cm3) was also carried out for a horizontally mounted cap & pin insulator. In this case, the snow accreted on the cap parts first but tended to be easily removed by its weight so that it never grew to bridge the sheds. Figs. 9 a & b show the snow accretion after the test. Since a cap & pin type insulator has a relatively larger shed diameter and spacing, snow accretion cannot easily grow to bridge sheds and tends to be removed by its weight.

Accreted snow on horizontally mounted cap & pin insulator (after the test). insulator string Widespread Blackout Triggered  Study of Contaminated Snow on Insulator Strings Screen Shot 2018 10 14 at 14
Accreted snow on horizontally mounted cap & pin insulator (after the test).
CLICK TO ENLARGE

A vertically mounted cap & pin insulator string was also tested (LWC 7% and volume density 0.4 g/cm3). At first, the snow accreted on the upper parts of the sheds and finally bridged the sheds in a packed condition. Fig. 10a shows the snow accretion just before bridging while Fig. 10b shows the comparison between the cap & pin and the porcelain long rod insulator tested at the same time. The time needed to bridge the cap & pin type was about 50 minutes but only about 10 min for the long rod.

insulator string Widespread Blackout Triggered  Study of Contaminated Snow on Insulator Strings Screen Shot 2018 10 14 at 14
Fig. 10a: Accreted snow on vertically mounted cap & pin insulator (after about 40 min.)
CLICK TO ENLARGE
insulator string Widespread Blackout Triggered  Study of Contaminated Snow on Insulator Strings Screen Shot 2018 10 14 at 14
Fig. 10b: Comparison between cap & pin and long rod insulator.
CLICK TO ENLARGE

Finally, tests were performed involving wet snow (LWC 7 % and volume density 0.3 g/cm3) on a horizontally mounted polymeric insulator over a duration of 30 minutes. The snow accreted on the core rod first and then gradually became packed, followed by bridging between the sheds. Figs. 11a & b show the snow accretion after the test. The shape of packed snow was like eccentric pennants into the wind. However, the snow tended to be easily blown off by wind in comparison with the porcelain long rod insulator. This might the result of a smaller core rod for the polymer in comparison with the long rod insulator – which results in a smaller area of contact between the surface and snow particles. As a result, in the case of polymeric insulators the shape of accreted snow was not cylinder-like but rather eccentric perpendicular into the wind.

insulator string Widespread Blackout Triggered  Study of Contaminated Snow on Insulator Strings Screen Shot 2018 10 14 at 14
Packed snow on horizontally mounted polymer insulator (after the test).
CLICK TO ENLARGE

The same test with wet snow (LWC 4 % and volume density 0.3g/cm3) was then carried out for a vertically mounted polymeric insulator for 50 min. A porcelain long rod insulator was also set in parallel for comparison. At first, the snow accreted on the upper part of the sheds, (Fig. 12a) and finally bridged and packed between the sheds.

Advertisement
insulator string Widespread Blackout Triggered  Study of Contaminated Snow on Insulator Strings INTEGRATED Engineering Software Mar 11

The time needed to bridge the polymeric insulator was about 20-30 min. versus about 10 min. for the porcelain long rod. Since shed spacing for the polymeric type is larger than for the porcelain long rod, the time to bridge it is about two to three times longer.

During the test, the polymeric insulator maintained high hydrophobicity (Fig. 13), but this property seemed to have little effect on snow accretion. In this regard it can be concluded that shed profile appears to be more important than shed material.

Fig. 12: Comparison of snow between polymeric and long rod insulator insulator string Widespread Blackout Triggered  Study of Contaminated Snow on Insulator Strings Screen Shot 2018 10 14 at 14
Fig. 12: Comparison of snow between polymeric and long rod insulator.
CLICK TO ENLARGE
Fig. 13: Hydrophobic surface of polymeric insulator (after test). insulator string Widespread Blackout Triggered  Study of Contaminated Snow on Insulator Strings Screen Shot 2018 10 14 at 14
Fig. 13: Hydrophobic surface of polymeric insulator (after test).
CLICK TO ENLARGE

Conclusions

1. Electrical failures of insulators by wet snow packed with sea-salt can be induced by unusual climatic conditions involving a great deal of wet snow with high conductivity combined with heavy winds. This phenomenon is quite distinct from the more commonly observed ice accretion or covered snow on insulator strings.

Advertisement
Desma Advertisement insulator string Widespread Blackout Triggered  Study of Contaminated Snow on Insulator Strings DESMA INMR OnlineAd

2. In order to clarify the failure mechanisms and establish effective countermeasures, the basic properties of the packed snow need to be better understood. To this end, artificial snow accretion tests have been performed on a qualitative basis as a first step toward future quantitative studies.

3. In these tests, several basic properties of packed wet snow were demonstrated and issues for future research identified, including:

a) The packed snow was reproduced on insulators using wet snow (LWC of 5-8%) whereas no snow accretion was seen using dry snow (LWC of 0%). This corresponds well with service experience that indicates that such outages are caused by packed, wet snow laden with contamination such as sea salt.

Advertisement
insulator string Widespread Blackout Triggered  Study of Contaminated Snow on Insulator Strings OFIL banner 300X125 July1

b) The cylinder-like shape of packed snow occurring in Niigata and triggering the widespread blackout of 2005 was reproduced on horizontally mounted long rod insulators and the mechanism of such a snow pack process was demonstrated. This mechanism – whereby snow grows by rotating along the insulator surface to become cylindrical – is basically the same as with snow accretion on conductors.

c) The shape of packed snow on vertically mounted long rod insulators in this test was eccentric pennant into the wind. While this shape shows some similarity with the packed snow on the polymeric arresters in Niigata, the cylinder like shape seen on many long rods was not reproduced. Test methodology or conditions may therefore have to be improved for any future research.

d) Shed profile affects the properties of wet snow accretion. Wider shed diameter and larger shed spacing results in lesser amounts of snow accretion and reduced possibility of bridging sheds. Therefore, cap & pin insulators perform the best and polymeric insulators are the next choice. Porcelain long rod insulators are the most vulnerable to packed snow. Bridging of the sheds can more easily occur on vertical than on horizontally mounted long rod insulators. This suggests that V-strings are most vulnerable and I-strings also become vulnerable as they sway due to winds.

e) The hydrophobicity of polymeric insulators seems to play little role in snow accretion. Shed profile is more important than shed material.

Advertisement
insulator string Widespread Blackout Triggered  Study of Contaminated Snow on Insulator Strings BG Big Box banner 300x250

f) Once snow bridges the sheds and becomes packed, it cannot easily be removed from the insulator surface. The adhesion tensile strength between the snow particles and between the insulator surface and snow particles is strong.

g) Water inside the packed wet snow tends to move downward and accumulate near the bottom of the insulator, making the LWC at the bottom larger than on other sections or even that of the original snow. While clarifying the flashover mechanism will be left for the future research, water migration may play an important role in this process.

Based on all these findings and the areas identified as requiring further research, another artificial wet snow accretion test having an improved test methodology is planned for the near future.