Thermal Inspections Help Florida Utility Prioritize Maintenance at Substations

November 18, 2017 • ARTICLE ARCHIVE, Inspection, Maintenance
CTC Logo
Ofil Systems

Among the best known technologies to assess the condition of power network assets are infrared and ultraviolet imaging. Both have been used now for decades and rely on specialized cameras that have evolved considerably over the years. The common direction of the latest generations of these cameras are towards more portability, improved data storage and sharing and greater ease for the user to assess the severity of any problem identified.

The continuing existence of both imaging technologies has made some power engineers wonder whether they are complementary and must always be used together or whether they are rather alternatives that detect the same incipient problems. The answer might vary depending on which expert is being asked. But what is clear is that each inspection technology offers its own specific benefits when it comes to locating particular types of defect.  

In general, it can be said that infrared (IR) imaging records presence of internal heat due to elevated leakage current while ultraviolet imaging detects presence of corona due to high electric field near surfaces. The first phenomenon depends on an internally-generated heat source and the second on surface condition. Both situations represent a potential hazard to continued safe operation of a line component or piece of equipment in a substation and both are a reason for either closer future scrutiny or immediate remedial maintenance.

When it comes to infrared imaging, there are not many experts who have been doing these types of inspections for so long that they have worked with several generations of equipment. Bill Hoth is one such person. With a professional background going back 33 years he has inspected a vast number of lines and substations – typically at a rate of some 700 per year. Last year, INMR accompanied Hoth on an infrared inspection of a 138 kV substation located near the Gulf Coast of Florida and discussed with him some of the specifics of the IR inspection process.


Bill Hoth recalls the day when the infrared equipment he took with him for inspections was so cumbersome that it required him to also tote nitrogen coolant. These days, as head of Clearwater-based Universal Thermography, he relies mainly on a camera with four times the pixels of the one it replaced yet that’s also light and portable. Hoth says he has maintained his focus only on infrared imaging – in large part because he found corona inspection too arbitrary and, in his view, unable to clearly identify whether a component was in good working order or not. By contrast, in the case of IR, the definitive factor in condition assessment is not absolute temperature but rather how temperature of the item being inspected compares to the reference temperature of similar nearby items. Says Hoth, “today, most engineers do not care that much about the temperature of any particular item but rather whether or not it is significantly different from similar objects located next to it.”

Hoth inspects distribution switches, a common area for ‘hot spots’. CLICK TO ENLARGE substation Thermal Inspections Help Florida Utility Prioritize Maintenance at Substations Screen Shot 2016 11 18 at 13

Hoth inspects distribution switches, a common area for ‘hot spots’.
CLICK TO ENLARGE

Hoth points out that IR imaging requires the inspector to be aware of key meteorological parameters since it is affected by humidity as well as wind conditions. For example, higher relative humidity makes any ‘hot spot’ appear cooler than it actually is. In the case of high wind, there is no specific camera adjustment, however a trained operator has to be aware of it and take it into account when preparing the inspection report. Hoth also notes that the key to all infrared imaging is emissivity since each item being inspected will emit at the same radiation as it absorbs. That means infrared imaging of each object has to be adjusted based on its known emissivity.

Thermal Inspections Help Florida Utility Prioritize Maintenance at Substations substation Thermal Inspections Help Florida Utility Prioritize Maintenance at Substations Screen Shot 2016 03 17 at 10

Infrared image of 500 kV substation switch with hot spot in receiver of switch. Repair involved tightening and adjusting receiver.

Thermal Inspections Help Florida Utility Prioritize Maintenance at Substations substation Thermal Inspections Help Florida Utility Prioritize Maintenance at Substations Screen Shot 2016 03 17 at 10

23 kV substation switch with hot spot. Hinge had to be adjusted and cleaned.

 

 

 

 

 

 

 

 