Protecting Composite Insulators from Corona

Advertisement
PPC Insulators [object object] Protecting Composite Insulators from Corona banner530x150 modified

One of the important design differences between silicone composite insulators and porcelain cap & pin or long rod types is their smaller shank diameter, made possible by the high strength glass-fibre reinforced core rod. However, this slimmer profile means smaller metal end fittings and the issue of corona then has to be considered, even at lower voltage levels. As far back as 1992, CIGRE WG B2.03 provided a general recommendation that, starting from 220 kV, the application of a suitable corona ring on the HV side is necessary, mainly because of the potential impact on RIV. Subsequently, research using specialized software became available to more accurately simulate how corona affected critical areas of a composite insulator (e. g. the triple point) as well as the effect of water droplet corona. Yet in spite of this progress, the threat posed by corona is still not always being dealt with properly.


Advertisement
GIG Advertisement [object object] Protecting Composite Insulators from Corona GIG Jun 28

In 2008, the IEEE Taskforce on Electric Fields and Composite Insulators published a paper that summarized the state of the art in this critical area. The paper not only highlighted the proposed corona protection designs offered by different manufacturers depending on voltage rating but also showed possible installation faults and provided assistance on modelling electric field. It also differentiated between electric field intensities that influence insulator string behaviour under dry as well as wet conditions (water droplet corona phenomenon). Three important thresholds (shown as rms values) were mentioned in this document and these must not be exceeded when the insulator string is being simulated under dry conditions with no pollution (see Table 1). The impact of air density also has to be considered in case of installation at altitudes significantly higher than sea level. Local rules typically provide the necessary correction factors in such cases.

[object object] Protecting Composite Insulators from Corona Screen Shot 2018 03 09 at 17
CLICK TO ENLARGE

In 2005, CIGRE WG B2.03 published a Technical Brochure (TB 284) titled Use of Corona Rings to Control the Electrical Field along Transmission Line Composite Insulators. Various 2-D and 3-D simulation programs were investigated that use finite element or boundary element methods. Comparison of results has shown that, if correctly used, these programs provide similar results. An interesting approach was adopted during this work involving 3-D simulations on two different types of 145 kV insulators. Laboratory tests were then conducted to measure the corona inception and extinction voltages on their HV end fittings in order to verify the simulations. The tests were performed at two different laboratories with the test configuration kept constant for each, i.e. same conductor, conductor clamp, height above ground, distance to steel cross-arm. This experimental configuration was also modelled using 3-D simulations of E-field. The voltage at which the electric field at the most exposed portion of the HV end fitting reached 22 kVrms/cm was then referred to as ‘calculated corona threshold voltage’ (see Table 2).

[object object] Protecting Composite Insulators from Corona Comparison Between Simulated Measured Corona Values
CLICK TO ENLARGE

Comparing calculated corona threshold with corona extinction voltages measured at the two laboratories, it was observed that the difference between measured and simulated values was less than 10% of the minimum value for Insulator Type 2 and even lower for Insulator Type 1. Moreover, the differences were such that, in all cases, the simulation tended toward lower values. Hence, if anything, the simulated results were always on the ‘safe’ side when it comes to design margins. TenneT’s Wintrack in the Netherlands – a highly innovative 420 kV compact double circuit line design – had to meet stringent values of acceptable electromagnetic field stress. This meant that for the composite insulators selected, permitted threshold of electric field was even lower than that specified from common practice in the U.S. To verify this, simulations were performed using finite element and boundary element methods and included modelling the neighbouring phases, insulators, hardware and conductors (see the FEM simulation in Fig. 3). These simulation models showed that neighbouring phases caused electric field to increase by about 10%, which then had to be taken into account when designing combined corona and power arc protection devices. Finally, after a successful demonstration that all these required values were fulfilled and that the protection devices also met aesthetic demands, full testing was completed. The phenomenon of corona on composite insulators has now been well documented. With the progress in computer speed and performance as well as the availability of suitable software programs, associated electric field stress on the insulator can be calculated, even after taking the overall structure near the string into account. Analysis of field data has also confirmed that empirically determined thresholds can be deduced from long-term experience. Still, care must be taken whenever new designs are developed or when there are innovative packages that combine new string hardware and insulators. Today, since cost is a driving force in line construction, design engineers must be aware that too great an emphasis on economics alone risks under-dimensioned components with only limited service lives.    

[object object] Protecting Composite Insulators from Corona Screen Shot 2018 03 09 at 18
Fig. 1a: Inappropriate corona protection of 245 kV string by hardware designed for cap & pin insulators.
CLICK TO ENLARGE
[object object] Protecting Composite Insulators from Corona Screen Shot 2018 03 09 at 18
Fig. 1b: Suitable corona protection of 245 kV string (combining corona and power arc protection).
CLICK TO ENLARGE
[object object] Protecting Composite Insulators from Corona Fi2a 300x191
Fig. 2a: 245 kV string with corona inception at 156 kV (no corona ring provided).
CLICK TO ENLARGE
[object object] Protecting Composite Insulators from Corona Fig2b 300x199
Fig. 2b: 245 kV string with corona inception at 220 kV (on armour rod).
CLICK TO ENLARGE
[object object] Protecting Composite Insulators from Corona Fig34
Fig. 3: Simulation of electric field on braced line post on lower corner left-hand side.
CLICK TO ENLARGE
composite insulator [object object] Protecting Composite Insulators from Corona Fig43
Fig. 4: Type testing of full scale braced line post using neighbouring phase on top.
CLICK TO ENLARGE