Principles for Selection of DC Insulation

Advertisement
PPC Insulators dc insulation Principles for Selection of DC Insulation banner530x150 modified

Since the dawn of transmission it became clear that pollution performance of insulators could have great impact on system reliability. Insulators installed close to pollution sources soon become covered by a potentially conductive surface layer that, when wetted by events such as fog or dew, results in discharge activity, also known as dry band arcing. In severe cases, this process can culminate in flashover and power disruptions.

The IEC published its first guide (IEC 815) for selecting insulators with respect to pollution back in 1986. With this much-debated document, the now well-known concept of creepage distance first became standardized. Although the guide quickly found widespread use worldwide due to its relative simplicity, application experience did not always prove successful. In highly polluted environments, for example, simply adding more creepage was not a guarantee of satisfactory service performance. Rather, research demonstrated that a number of other insulator parameters, such as shape (profile) and material, also had to be taken into account.

By the early 1990s, it became clear that IEC 815 needed substantial revision to address such deficiencies and also to accommodate the newest insulator technologies. A large-scale project was therefore begun aimed at revising and updating this standard to cover AC and DC as well as all the different types of insulator technologies – ceramic, glass and polymer. In the process, IEC relied on Cigré working groups to provide sound technical support.

The work started in 1994 within SC 33 and the result was a reference document that would form the basis for future guidelines. This ‘review of current knowledge’ document proved sizeable, with 200 pages and 382 references, and was published in 2000 as Cigré Brochure 158. Work subsequently continued with development of guidelines for selecting and dimensioning outdoor insulators for AC systems, published in 2008 as Cigré Brochure 361. The last task then became to develop similar guidelines for DC systems, finally issued in December 2012 as Cigré Brochure 518.

This INMR article from 2014 by industry expert Chris Engelbrecht, who was closely involved as Convener of the WG, reviews this latest brochure as well as some of its basic principles.


Detailed design process is necessary for DC systems because of great impact of either over-dimensioned or underperforming insulation. dc insulation Principles for Selection of DC Insulation Screen Shot 2017 02 24 at 10
Detailed design process is necessary for DC systems because of great impact of either over-dimensioned or underperforming insulation.
CLICK TO ENLARGE

DC Versus AC Pollution Flashover

Important differences between development of pollution flashover under DC versus AC energization can be summarized as follows:

Advertisement
GIG Advertisement dc insulation Principles for Selection of DC Insulation GIG Jan 22

1. DC energized insulators accumulate more pollution since, under low wind speeds, electrostatic attraction of pollution particles under unidirectional electric field dominates deposition by aerodynamic action. On AC energized insulation, by contrast, there is little to no attraction of pollutants by the alternating electric field. Indeed, research measurements suggest that the ratio of DC to AC pollution deposition in the same service environment can vary significantly and in some cases by as much as a factor of 10.

2. With the absence of voltage zeros, dry band arcing under DC is more likely to grow into flashover. This differs from the case under AC where dry band arcs must re-ignite after each voltage zero. DC dry band arcs are also more mobile and likely to leave the insulator surface to propagate through air. This requires development of special DC insulator profiles to ensure the effectiveness of the creepage distance. Another result of this difference in flashover development is that the relative flashover strength of DC insulation deteriorates more, compared to AC insulation, for any given increase in pollution severity (illustrated conceptually in Fig. 1.)

dc insulation Principles for Selection of DC Insulation Research suggests that the ratio of DC to AC pollution deposition in the same service environment can vary by as much
Research suggests that the ratio of DC to AC pollution deposition in the same service environment can vary by as much as a factor of 10.
CLICK TO ENLARGE
Fig. 1: Relative AC versus DC pollution flashover stress (FOV) as function of pollution severity. dc insulation Principles for Selection of DC Insulation Relative AC versus DC pollution flashover stress as function of pollution severity
Fig. 1: Relative AC versus DC pollution flashover stress (FOV) as function of pollution severity.
CLICK TO ENLARGE

 

 

 

 

 

 

 

 

 

 

3. Relative to other insulation stresses, the pollution performance of insulators is usually the parameter that dictates insulation design for HVDC systems. This differs from AC systems where insulation distances are typically determined by required lightning or switching performance of the line or substation (illustrated in Fig. 2 for EVH and UHV system voltages).

Fig. 2: Comparison of indicative insulation distance requirements (glass and porcelain) for switching (blue) lightning (red) and pollution (green) for HVAC and HVDC systems. dc insulation Principles for Selection of DC Insulation Comparison of indicative insulation distance requirements glass and porcelain for switching blue lightning red and pollution for HVAC and HVDC systems
Fig. 2: Comparison of indicative insulation distance requirements (glass and porcelain) for switching (blue) lightning (red) and pollution (green) for HVAC and HVDC systems.
CLICK TO ENLARGE

Fig. 2 also shows that extreme insulation lengths may be necessary in polluted areas, forcing system planners to reconsider any project and evaluate alternatives such as different line routes (i.e. avoiding polluted areas) or implementing cables or indoor switchyards – all in order to minimize the number of external insulation surfaces.There is therefore an urgent need to look at insulation design for HVDC systems at the earliest stages of a project and much sooner than would be customary for AC systems. It is also much more important to follow a detailed design process because of the potentially huge impact of either over-dimensioned or underperforming insulation.

Advertisement
dc insulation Principles for Selection of DC Insulation CSL Advertisement e1477326535980

Holistic Flow Chart Methodology

In the Cigré guidelines, designers are encouraged to follow an exhaustive approach with the aim of minimizing uncertainties in input data and the resulting impact on final design. Dimensioning principles are introduced based on a flow chart (Fig. 3) to provide a holistic overview and context for each activity required.

Overall design strategy is shown in the vertical column of numbered blocks on the left. A number of alternatives for obtaining the relevant information are then presented such that the further right one moves the less certain the results. For example, when determining site pollution severity, information collected from existing DC lines will provide far more accurate results than a purely qualitative estimation.

Fig. 3: Insulator selection flow chart. dc insulation Principles for Selection of DC Insulation Insulator selection flow chart
Fig. 3: Insulator selection flow chart.
CLICK TO ENLARGE

The various activities in the flowchart can be summarized as follows:

1. Identify Candidate Insulators

Due to the special demands, some insulator types are specifically optimized for HVDC applications in terms of insulating materials and shed profiles and there is limited choice available. Nevertheless, choices still need to be made in regard to type, insulating material and profile for insulators that will be utilized at any particular location. Initial selection of a candidate insulator is usually based on a simplified preliminary site assessment. This choice could then be revised over time as more detailed information about site conditions becomes available.

2. Assess Environmental & System Stresses

Ideally, pollution deposition measurements over several years are needed to provide accurate data on the nature and severity of pollution at any given site. In the case of DC applications, it is especially important these measurements be performed on insulators that are energized to a representative DC stress. Since this is not always feasible, other techniques may have to be employed to obtain this information.

Advertisement
BPG International Advertisement dc insulation Principles for Selection of DC Insulation BPG logo

For example, if there is data on performance of HVAC installations in the area, it may be possible to ‘translate’ this to HVDC. But such a methodology is purely indicative and the designer must still make assumptions about differences in pollution accumulation on DC versus AC energized insulators. It is also possible to use a general environmental assessment to identify a comparable environment in a different location where an HVDC installation is already in operation. Data from this installation could then be useful in insulation design and selection for the new project.

For critical installations such as converter stations there is need for detailed site severity assessment, e.g. by setting up experimental stations at representative locations to obtain estimate of long-term pollution accumulation. dc insulation Principles for Selection of DC Insulation For critical installations such as converter stations there is need for detailed site severity assessment e
For critical installations such as converter stations there is need for detailed site severity assessment, e.g. by setting up experimental stations at representative locations to obtain estimate of long-term pollution accumulation.
CLICK TO ENLARGE

3. Determine Insulator Characteristics & Dimensions

The most accurate way to select insulators for any new installation is to directly determine risk of flashover based on service experience of DC lines and substations in the same area or having similar environmental conditions. Flashover risk can also be obtained utilizing test stations where performance of a range of pre-selected insulators is monitored under DC voltage at locations considered representative of the new line and station corridor.

Where there is previous experience with DC lines in the same area, excellent data on insulator performance is available on which to base preliminary design. If there is a lead-time of a year or more, good data can also be obtained from installing energized insulators at field stations sited at representative locations along the line as well as at the converter station. Insulators at such field stations must be energized to representative stresses to take account of the significant influence of electrostatic field on pollution accumulation.

Instead of determining risk of flashover directly, it is also possible to follow a simplified deterministic approach during design. In this simplified method, pollution stress (i.e. maximum pollution on the insulator) is determined from measurements and through site condition studies. Insulator strength is then estimated from published information or based on performance data summarized in guidelines with correction factors applied to correlate test conditions with actual site conditions. Such data are then used to make a rough selection of insulator type, material and dimensions.

4. Verify Design

This is the last step in the process whereby the chosen insulation design is evaluated either by comparison with past experience or by testing.

Simplified Dimensioning Process

Besides the detailed dimensioning method discussed above, the Cigré WG also proposed a simplified method with the basic intent to:

• provide useful orientation at the project’s start and identify a range of preliminary solutions;

• analyze outage performance and the adequacy of insulation solutions on existing systems.

It is important to stress, however, that this simplified method has serious limitations which may result in either over or under-dimensioned insulation and is therefore not considered accurate enough for the final design process. On the other hand, it does provide insight into the various parameters that must be taken into account when dimensioning insulators for HVDC with respect to pollution.

Advertisement
dc insulation Principles for Selection of DC Insulation INTEGRATED Engineering Software Mar 11

The first part deals with determining site pollution severity, which is the equivalent value of ESDD at a 0.1 mg/cm2 reference value of NSDD. The second step is to adjust this value individually for each type of insulator being considered so that the required USCD can be determined.

Determining Site DC Severity

An overview of the process to determine DC severity is presented in Fig. 4. The aim of such a site assessment is to obtain an accurate picture of contamination severity of the area concerned based on data collected over a relatively long period. Initial assessment is usually based on:

1. Collected performance data on existing lines or substations, preferably DC energized, although AC data could also be useful;

2. Identification of type (i.e. A or B, as defined in IEC 60815-1), and composition of pollutants (i.e. type of salts, non-soluble deposits etc.);

3. Measurement of quantity of pollution present;

4. Characterization of climate, specifically if there is a prolonged dry season;

5. Assessment of geographic, topological and geological features to identify possible contamination sources, and;

6. Survey of present and foreseeable future pollution sources and land use.

Fig. 4: Part 1 of simplified dimensioning process – Determining site DC severity. dc insulation Principles for Selection of DC Insulation Part 1 of simplified dimensioning process Determining site DC severity
Fig. 4: Part 1 of simplified dimensioning process – Determining site DC severity.
CLICK TO ENLARGE

For critical installations such as converter stations, the above information may not prove accurate enough and therefore there is a need for a more detailed assessment. Ideally, this includes setting up experimental stations at representative locations equipped with selected different DC energized insulators so as to obtain an estimate of long-term pollution accumulation.

An alternative approach, but with increased uncertainty, is to base site severity assessment on measurements taken on AC energized or non-energized insulators. In such a case, it becomes necessary to estimate the contribution of electrostatic field on pollution accumulation on energized DC insulators. This is done with the DC/AC accumulation factor Kp (applicable to both ESDD and NSDD values). This factor can vary between 1 and 10 but, for the simplified dimensioning process, values between 1 and 3 are more typical.

Once site severity measurements become available, the maximum value of the average ESDDs measured on insulators is converted to an equivalent laboratory test severity. With this correction, it is recognized that artificial testing differs from natural pollution in a number of important aspects, namely:

• Type of salt

Laboratory testing is generally performed with marine salt (NaCl) whereas natural pollution layers often contain less soluble salts such as gypsum (CaSO4). At present, there is still no widely applicable methodology to quantify this effect other than performing specific flashover testing on insulators with natural pollution, so assume Kc=1.

• Amount of non-soluble material

Present in the pollution layer The standardized laboratory test usually subjects an insulator to a pollution layer with a non-soluble deposit density (NSDD) of 0.1 mg/cm2. In service, NSDD levels typically vary from 0.01 to 10 mg/cm2. The measured ESDD is normalized to an NSDD value of 0.1 mg/cm2 with a factor, Kn.

These corrections result in an estimate of equivalent site severity at an NSDD=0.1 mg/cm2, defined as the DC site severity.

Advertisement
Yizumi Ad dc insulation Principles for Selection of DC Insulation INMR YIZUMI July edition

Determining Required Creepage Distance

The required insulator dimensions (notably creepage distance) are determined from available service experience or test results. If such data is not available, representative tests can be performed on candidate insulator types to determine their statistical flashover properties. The term ‘representative test’ is understood to mean any laboratory test designed to duplicate natural contamination conditions as closely as possible in terms of 1. pollution severity (i.e. ESDD and NSDD), 2. its composition (i.e. type of salt as well as non-soluble components), 3. uniformity of the deposit and 4. type of wetting conditions.

Alternatively, standard laboratory pollution test results can also be utilized but then a number of adjustments to the DC severity become necessary. These adjustments depend on specific insulator type and are therefore done separately for each different insulator that will be utilized (see Fig. 5).

Fig. 5: Part 2 of simplified dimensioning process – Determining required USCD. (This part of process performed separately for each insulator type). dc insulation Principles for Selection of DC Insulation Part 2 of simplified dimensioning process  E2 80 93 Determining required USCD
Fig. 5: Part 2 of simplified dimensioning process – Determining required USCD. (This part of process performed separately for each insulator type).
CLICK TO ENLARGE
Non-uniform pollution deposition on ± 500 kV DC wall bushing can impact flashover voltage. dc insulation Principles for Selection of DC Insulation Non uniform pollution deposition on  C2 B1 500 kV DC wall bushing can impact flashover voltage
Non-uniform pollution deposition on ± 500 kV DC wall bushing can impact flashover voltage.

 

 

 

 

 

 

 

 

Briefly the adjustments can be described as follows:

• Non-uniformity of contamination layer

The flashover voltage of non-uniformly polluted insulators can be significantly higher than for uniformly polluted ones. This effect is corrected for with a factor Kcur.

• Insulator diameter

Larger diameter insulators collect less contamination than small diameter ones. This effect is corrected for with a factor Kd.

• Statistical considerations

This correction factor, Ks, is chosen to obtain a sufficiently low risk of flashover.

Application of these various correction factors results in a design DC severity that corresponds to the pollution severity at which representative laboratory tests can then be performed. At this stage, it is also possible to make a first estimate of leakage distance (unified specific creepage distance: USCD) required for the project, based on the graphs in Fig. 6. Two graphs are shown, one for hydrophobicity transfer materials (HTM) such as silicone rubber and the other for non-HTM insulators such as glass or porcelain.

dc insulation Principles for Selection of DC Insulation Median DC flashover characteristics worst case for hydrophobicity transfer and non hydrophobicity transfer material insulators as determined from solid layer laboratory test results
Fig. 6: Median DC flashover characteristics (worst case) for hydrophobicity transfer (HTM) and non-hydrophobicity transfer material insulators as determined from solid layer laboratory test results.
CLICK TO ENLARGE
DC installations at higher altitudes require adjusting leakage distance for the lower flashover voltage under low air density. dc insulation Principles for Selection of DC Insulation DC installations at higher altitudes require adjusting leakage distance for the lower flashover voltage under low air density
DC installations at higher altitudes require adjusting leakage distance for the lower flashover voltage under low air density.
CLICK TO ENLARGE

 

Advertisement
Desma Advertisement dc insulation Principles for Selection of DC Insulation Desma banner Apr 26

 

 

 

 

 

 

 

 

 

 

These graphs are valid for line as well as substation insulators having relatively small diameter. Insulators with larger diameters generally have a lower flashover voltage than those with smaller diameters and therefore require longer leakage distances. This effect is corrected for with factor Cd. At present, it is not deemed necessary to correct for the effect of diameter when it comes to hydrophobic insulators.

For installations at high altitude an additional correction factor can be considered to adjust leakage distance for the lower flashover voltage under low air density conditions. This is corrected for by a factor, Ca.

Verification

As confirmation of the applicability of the simplified method, the Cigré working group analyzed actual outage performances for various installations against the design curves presented. However, this proved difficult since detailed information on outage performance and corresponding pollution severities for HVDC systems in service are not generally published. Still, some useful information was found and the results of this analysis are presented separately for substations (Fig. 7), lines (Fig. 8) and HTM insulators (Fig. 9). In these graphs a distinction is made as follows:

 

DC Insulation dc insulation Principles for Selection of DC Insulation DC stations Collected field experience on
Fig. 7: DC stations: Collected field experience on non-HTM converter station insulators. Data normalized using the simplified method.
CLICK TO ENLARGE
Fig. 8: DC overhead lines: Collected field experience on non-HTM insulators. dc insulation Principles for Selection of DC Insulation DC overhead lines Collected field
Fig. 8: DC overhead lines: Collected field experience on non-HTM insulators.
CLICK TO ENLARGE

 

 

 

 

 

 

 

 

 

 

Fig. 9: HTM Insulators: Collected field experience. dc insulation Principles for Selection of DC Insulation HTM Insulators Collected field experience
Fig. 9: HTM Insulators: Collected field experience.
CLICK TO ENLARGE

• Design values

These data points represent minimum creepage distance values implemented on actual HVDC systems but for which performance data is not yet available.

• Good performance

Indicates minimum creepage distance values implemented on actual HVDC systems for which positive service experience has been reported.

• Flashovers

Indicates minimum creepage distance values implemented on actual HVDC systems for which negative service experience has been reported.

Data in these figures basically confirms the appropriateness of the simplified method recommended for obtaining a realistic first estimate of the insulation dimensions required at HVDC installations.